High Power Applications Above 5kA Demand a New Approach to Current Measurement

The power utilities business is changing globally. Where once the main provides of electrical power were coal, gas, oil or even nuclear power stations, today renewable sources of power, such as wind and solar are becoming significant. 2020 was the best year on record for wind, with 93 GW of new capacity installed globally, representing – a 53 per cent year-on-year increase. And this trend is set to continue as the world aims to achieves net zero for carbon emissions by 2050.

By Loic Moreau, VP Technical Marketing, Danisense

A new report published by the Global Wind Energy Council (GWEC) argues that the world needs to install wind power three times faster over the next decade in order to avoid the worst impacts of climate change.

This is driving huge changes in all aspects of the electrical power industry, including the methods used to measure large currents. The great advantage of traditional fossil fuel power stations is that the supply is very stable and can be controlled and regulated eas- ily. With renewables, the source of the electrical power is volatile – power is not generated unless, for example, the wind blows. DC currents from photovoltaic installations or the power converters used in other renewables can be injected into the traditional AC grid, therefore conventional large current measurement tech- niques are not appropriate.

Another associated trend concerns large batteries. In order to use electrical power when it is required – not just when it is being gen- erated – huge battery systems are being constructed. One particu- larly apposite example is to be found in Monterey Bay, California, where the Moss Landing Power Plant, once California’s largest elec- tric power station fuelled by natural gas, now houses the world’s largest battery, storing excess energy when solar panels and wind farms produce electricity and feeding it back into the grid when they are idle. 

Phase 1 of the renamed Moss Landing Energy Stor- age Facility began operation in December 2020 with a capacity of 300MW / 1,200MWh. Phase 2 of the project, due for completion in August 2021, will add another 100MW / 400MWh. Such enormous installations also require very accurate high current measurement.

Again, conventional methods have proved to be inadequate for the task.

Instead, applications requiring the measurement of currents above 5kA are increasingly looking at zero-flux techniques that use the magnetic field generated by the circulation of the current, such as Danisense’s Fluxgate technology.

Principles of zero-flux current transducer operation
closed loop current transducer principle
closed-loop principle

Zero-flux technology

To explain the operation of zero-flux technology, it is appropriate to first consider some basic principles. In Figure 1, a pick-up coil con- structed around a magnetic bar is shown top left; at top right the equivalent electric circuit is shown with resistor and an inductance. When a voltage is applied, the current in the circuit is shown in the red curve. The current grows progressively, following the slope ac- cording to the value of the inductance, up to the point where the inductance saturates. At this condition, the equivalent electric cir- cuit can be considered to be resistive only.

When creating a zero-flux current transducer, the material used for the pick-up bar has specific magnetic properties which cause the current to follow the blue curve. Initially, the current grows slow- ly due to a high impedance value. Then, abruptly, the inductance saturates and the current increases very rapidly to achieve the end point as previously.

If a square voltage signal is now applied, the profile of the current becomes a succession of positive and negative saturation and de- saturation cycles. If a conductor is placed close to the Fluxgate element, the circulation of the current will create an additional magnetic field which will influence the signal by shifting the zero position (Figure 2a – blue curve). Finally, signal processing per- formed on the second harmonic reveals details about the primary current (Figure 2a – purple curve).

To improve the performance of the current sense transduced even further, manufacturers often combine zero-flux technology with the closed loop principle, shown in Figure 2b. Here, the Fluxgate element is placed in the air gap and during the measurement of the magnetic field, the current output is re-injected through the sec- ondary winding which then generates a magnetic field in the oppo- site direction. Using this method, the magnetic field experienced by the Fluxgate is always zero, eliminating offset and linearity issues.

Four main zero-flux topologies are currently available (Figure 3). The first (3a) is based on a magnetic core with an air gap, plus the secondary winding. It resembles a closed loop Hall Effect cur- rent transducer, where the Hall element in the air gap has been replaced by the Fluxgate. The main benefit is a good offset drift. The second topology (3b) is a single core which takes the role of the Fluxgate element. As there is no air gap, one of the key ben- efits is its EMC robustness and also its high resolution. But as the saturation of the core occurs quickly, the bandwidth is limited to a few Hertz. The third topology solves this issue by adding a wind- ing core (3c) which only measures the AC signal, as with a current transformer. In that case, you get all the benefits. However, if an even higher performance is required, a ‘balanced core’ (3d) topol- ogy employs two identical Fluxgate elements placed in opposition. Therefore, whatever the external environment conditions – such as EMC or temperature variations – there is a natural passive com- pensation between the two sensing elements. Using this approach, it is possible to achieve a measurement accuracy of 1ppm, even in harsh environments.

Zero flux technology
Danisense 11kA current sense transducer
Danisense sensing head in a wind turbine installation

Fluxgate technology can be used to provide very accurate, stable and repeatable current measurement for all current levels and Danisense has developed a family of current sense transducers covering 0-600A, 600-3000A and above 3kA. For the emerging mar- kets with very high currents as discussed in the first part of this ar- ticle, Danisense has had to address new challenges, but is currently developing solutions up to 30kA and can see no theoretical limit for the Fluxgate approach.

Isolation and safety are key requirements in high power applica- tions. The governing standard is IEC 61010. Unlike products that the company offers for lower current applications, Danisense’s DR50000IM (8kA) and DR10000IM (11kA) current sense transduc- ers (Figure 4) separate the sensing head from the electronics signal processing unit.

The sensing head is a rugged, passive device that can be positioned and left for long periods in noisy electrical environments without being affected by any interference which will inevitably be present, given the high currents involved. The complex signal condition- ing and processing can be done remotely in a safe, temperature- controlled benign laboratory environment, which can be 30m away from the sensing head. By separating the functions of the current sense transducer in this way, the passive sensing head can also be made rugged enough to cope with challenging environmental con- ditions. Also, it is dangerous to work close to a high magnetic field environment so this approach minimizes the need for operators to manipulate the transducer – for example to connect the power supply and the output – in the magnetic field, increasing safety.

Danisense 30kA sensing head

Danisense’s new high current transducers also feature a low exci- tation frequency of 7kHz. For smaller products, a much higher ex- citation frequency of up to 32kHz is preferred as this improves the dynamic performance. However, for the DR series sensors saturat- ing such big magnetic core with high frequency would require high power circuitry which can be large and expensive. By reducing the frequency Danisense has been able to achieve a good balance be- tween dynamic performance and power level.

Figure 5 shows the Danisense’s DR10000IM sensing head in a Sie- mens Gamesa wind turbine installation.

A specially designed cable with multiple twisted pairs featuring in- dividual shielding encompassed by a second overall shielding layer is used to connect the sensing head and the electronic processing stage. If the distance between the head and the processing unit is over 30 meters Danisense uses three wires for the compensated current instead of one to reduce the current value and then the impedance effect.

Danisense’s DR50000IM and DR10000IM current sense transduc- ers have a high bandwidth of 100kHz and are ultra-stable with a linearity error of only 1ppm. The company also offers equivalent voltage output versions of these transducers – DR50000UX (8kA) and DR10000UX (11kA)

Conclusion

With the introduction of the smart grid, utilities companies and oth- ers are having to reconsider the current measurement techniques they employ, because electrical power is being generated from a much wider range of sources that ever before. Danisense’s Flux- gate technology – already employed extensively in applications such as MRI scanners, EV charging stations and large physics in- stitutions such as CERN – is proving equally capable of handling high currents in the tens of kiloamperes, delivering accurate, stable and repeatable measurement results. Danisense knows that in the near future there will be a need to measure even higher currents, and will shortly launch a current sense transducer with the capabil- ity of measuring up to 30kA (Figure 6). This will feature a 330mm aperture – the largest ever offered by Danisense – which will also be of interest to companies which have a lower current demand but which have large diameter cables.